The absorption cycle, in dryer terms
Five stages, drawn as the circuit actually is: an evaporator that chills the process air, an absorber that holds the vacuum, a pump that lifts liquid, a generator that takes heat, and a condenser that is not a waste-heat exchanger but the dryer's heater.
2.1 The loop
The chilling duty
Evaporation
Low-pressure liquid refrigerant enters the evaporator, which in this appliance is the process-air cooling coil.
The vessel is held under deep vacuum. Water at 5 °C boils at roughly 0.87 kPa, about one hundredth of atmospheric pressure, so the refrigerant evaporates at the temperature of the process air rather than at 100 °C.
Evaporation draws latent heat out of that air. Two transfers therefore occur across the same coil face: the process air is cooled below its dew point and its moisture condenses onto the coil, while the refrigerant boils and carries that heat away as vapor.
Evaporator 5–15 °C · 0.9–1.7 kPa · heat in from process air
2.2 State points
The values below are design targets for a single-effect lithium bromide machine sized to a domestic dry cycle. They are not measured data and will move with ambient, load and control strategy.
| Point | Medium | Temperature | Pressure | Function |
|---|---|---|---|---|
| Evaporator inlet | Refrigerant liquid | 5–10 °C | 0.9–1.2 kPa | Flashing; chills process air |
| Evaporator outlet | Refrigerant vapor | 5–10 °C | 0.9–1.2 kPa | To absorber |
| Absorber outlet | Dilute LiBr solution | 35–40 °C | ≈ 1 kPa | To solution pump |
| Generator inlet | Dilute solution | 70–80 °C | 7.4–12.3 kPa | After solution heat exchanger |
| Generator outlet — vapor | Refrigerant vapor | 80–90 °C | 7.4–12.3 kPa | To condenser |
| Generator outlet — solution | Concentrated LiBr | 88–95 °C | 7.4–12.3 kPa | To heat exchanger, then throttle |
| Condenser outlet | Refrigerant liquid | 40–50 °C | 7.4–12.3 kPa | To expansion device |
| Process air, coil outlet | Air, saturated | 10–15 °C | Ambient | To reheat coil |
2.3 The process-air loop
The absorption circuit does not dry the clothes by itself. It chills and re-warms a closed air stream, and that stream does the drying.
Drum outlet
Warm air leaves the drum, saturated
Carrying the moisture the load has given up, at 40–70 °C depending on regime.
Evaporator
Chilled below its dew point
Refrigerant boiling at 5–15 °C takes sensible and latent heat out of the air. Water condenses on the coil and drains away.
Condenser
Reheated by the cycle's own reject heat
The same heat just removed is returned to the air at 45–60 °C, leaving it warm and dry.
Return
Back to the drum
The loop is closed. No air leaves the appliance and no duct is required.
The point of the whole design
2.4 Why water and lithium bromide
Working fluid pair selection
Two binary pairs dominate absorption practice: water as refrigerant with lithium bromide as absorbent, used for air conditioning and chilling; and ammonia as refrigerant with water as absorbent, used where sub-freezing evaporator temperatures are required. A clothes dryer requires the first.
- The evaporator never needs to go below 0 °C.Process air only needs cooling to a few degrees above freezing. Water's freezing point is a constraint the duty never reaches, not a limitation.
- Water is the refrigerant.Zero ozone-depletion potential, zero global-warming potential, non-toxic, non-flammable, inexpensive, and already present in the appliance as condensate.
- Lithium bromide is non-volatile.The vapor leaving the generator is essentially pure water, so no analyzer or rectifier is needed. Ammonia–water systems require both to strip trace water from the vapor before condensation.
- Ammonia is the wrong material for a home.It is toxic and flammable. Introducing an ammonia charge into a consumer laundry appliance creates a risk that no efficiency gain justifies.
The penalties accepted in exchange are deep-vacuum operation and a corrosive brine. Neither is trivial, and both are carried in the risk register at section 05 rather than dismissed here.